Application: | Insulators |
---|---|
Type: | Oip Bushing |
Chemistry: | Inorganic Insulation |
Material: | Silicone |
Thermal Rating: | 250 250 |
Maximum Voltage: | >100KV |
Customization: |
---|
Suppliers with verified business licenses
Standard IEC 60137-2017 | |||||||||||||
Highest Voltage of Equipment Um | kV | 24 | 24 | 24 | 24 | 36 | 36 | 36 | 36 | 52 | 52 | 52 | 52 |
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 |
Power Frequency Withstand Voltage | kV | 55 | 55 | 55 | 55 | 77 | 77 | 77 | 77 | 105 | 105 | 105 | 105 |
Lightning Impulse Withstand Voltage | kV | 125 | 125 | 125 | 125 | 170 | 170 | 170 | 170 | 250 | 250 | 250 | 250 |
Rated Current | A | 10000 | 16000 | 25000 | 31500 | 10000 | 16000 | 25000 | 31500 | 10000 | 16000 | 25000 | 31500 |
Temperature | ºC | Outdoor: -60ºC ~ +55ºC |
Some Information about the OIP Capacitive Bushing of RIB
Suppliers with verified business licenses